Troubleshooting
Use this table for troubleshooting help.
Symptom |
Possible cause |
Remedy |
Alarm is sounding even though the mains is normal. |
The AC input power is not connected well. |
Check if input power cord firmly connected to the mains. |
The AC input is connected to the UPS output. |
Plug AC input power cord to AC input correctly. |
|
|
EPO function is activated. |
Set the circuit in closed position to disable EPO function. |
|
Line and neutral conductors of UPS input are reversed. |
Rotate mains power socket by 180° and then connect to UPS. |
|
The external or internal battery is incorrectly connected. |
Check if all batteries are connected well. |
Fault code 27 is on the display, and the alarm is continuously sounding. |
Battery voltage is too high or the charger is fault. |
Contact your dealer. |
Fault code 28 is on the display, and the alarm is continuously sounding. |
Battery voltage is too low or the charger is fault. |
Contact your dealer. |
|
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. |
Remove excess loads from UPS output. |
After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains. |
Remove excess loads from UPS output first. Then shut down the UPS and restart it. |
|
Fault code 49is on the display, and the alarm is continuously sounding. |
UPS is over input current. |
Remove excess loads from UPS output. |
Fault code 43 and |
The UPS shut down automatically because of overload at the UPS output. |
Remove excess loads from UPS output and restart it. |
Fault code 14 is on the display, and the alarm is continuously sounding. |
The UPS shut down automatically because short circuit occurs on the UPS output. |
Check output wiring and if connected devices are in short circuit status. |
Fault codes 01, 02, 03, 11, 12, 13 and 41 are on the display, and the alarm is continuously sounding. |
A UPS internal fault has occurred. There are two possible results: 1. The load is still supplied, but directly from AC power via bypass. |
Contact your dealer |
Battery backup time is shorter than nominal value. |
Batteries are not fully charged |
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer. |
Battery defect |
Contact your dealer to replace the battery. |
|
Fault code 2A is on the display, and the alarm is continuously sounding. |
The short circuit occurs on the charger output. |
Check if battery wiring of connected external pack is in short circuit status. |
Fault code 45 is on the display, and the alarm is continuously sounding. |
The charger does not have output and battery voltage is less than 10V/PC. |
Contact your dealer. |